What goes in the fire alarm log book
The log book is the record the servicing engineer reviews at each visit. The 2025 edition of BS 5839-1 includes a model log book format, accepts digital or paper log books, and expects agreed variations to be recorded in it.
Next service due 15 Dec 2026.
Any date from 15 Nov 2026 to 15 Jan 2027 is inside the 5 to 7 month window that BS 5839-1:2025 allows after the visit on 15 Jun 2026.
Service visits for the next two years
| Visit | Earliest | Due | Latest | Also at this visit |
|---|---|---|---|---|
| 1 | 15 Nov 2026 | 15 Dec 2026 | 15 Jan 2027 | ARC signals, panel clock, false alarm rate |
| 2 | 15 May 2027 | 15 Jun 2027 | 15 Jul 2027 | 12 months on: duct smoke detectors |
| 3 | 15 Nov 2027 | 15 Dec 2027 | 15 Jan 2028 | ARC signals, panel clock, false alarm rate |
| 4 | 15 May 2028 | 15 Jun 2028 | 15 Jul 2028 | 12 months on: duct smoke detectors |
Assumes each visit happens on its due date. If your last visit was not a 12-monthly one, the 12-monthly items fall on visits 1 and 3 instead. Every visit checks ARC signals, the panel clock and the false alarm rate.
Weekly call point rotation
With 10 call points, each one is operated once every 10 weeks, so about 5.2 times a year by the weekly test alone.
| Week | Date | Call point | Result | Signature |
|---|---|---|---|---|
| 1 | Mon 4 Jan 2027 | CP 1 | ||
| 2 | Mon 11 Jan 2027 | CP 2 | ||
| 3 | Mon 18 Jan 2027 | CP 3 | ||
| 4 | Mon 25 Jan 2027 | CP 4 | ||
| 5 | Mon 1 Feb 2027 | CP 5 | ||
| 6 | Mon 8 Feb 2027 | CP 6 | ||
| 7 | Mon 15 Feb 2027 | CP 7 | ||
| 8 | Mon 22 Feb 2027 | CP 8 | ||
| 9 | Mon 1 Mar 2027 | CP 9 | ||
| 10 | Mon 8 Mar 2027 | CP 10 |
False alarm rate
1 / 40 x 100 = 2.5 false alarms per 100 detectors per year. Under 4 per 100. The servicing engineer still checks the rate at every visit.
Runs in your browser; nothing you type is sent anywhere. England and Wales.
What to record
- Every weekly test: date, zone, the call point or detector used, door releases, the result, any fault and the action taken, and a signature.
- Every false alarm: its category, the date and time, and why it happened if known. See false alarm rate.
- Every fault, and how it was put right.
- Every service visit and who did it.
- Agreed variations from the standard.
The name and phone number of the servicing company should be displayed at the main control panel.
Sources: South Wales Fire and Rescue Service log book, FIA guidance on certificates and log books, IET Wiring Matters, November 2025, FIA guide to the 2025 changes. BS 5839-1 is sold by BSI and we have not reproduced it; the wording here is ours.
Printable weekly test sheet
| Date | Zone | Call point or detector | Door release | Result | Fault and action taken | Signature |
|---|---|---|---|---|---|---|
Print this page. The planner above prints as a dated rotation for your own call points.
Before you rely on these dates
- The rules here come from published summaries of BS 5839-1:2025 by the Fire Industry Association and the IET, and from fire and rescue service log book guidance, each linked on the page it is used. The standard itself is sold by BSI, so the wording on this site is ours.
- The planner works out dates, a rotation and a rate. It does not certify a system or replace a fire risk assessment.
- Your servicing company decides what each visit covers and issues the certificate. If their schedule differs, theirs is the one to follow.
- England and Wales. Scotland and Northern Ireland have their own fire safety law.
Questions
Can the log book be digital?
Yes. The 2025 edition accepts a log book in digital or paper form.
What are the false alarm categories?
Fire and rescue service log books use unwanted alarms, equipment false alarms, malicious false alarms, false alarms of good intent, and unknown.