Fire Alarm RegisterAll guides

Fire alarm service and weekly test planner

Enter the date of the last service visit (or the date a new system was accepted), how many manual call points the system has, and the day the weekly tests start. You get the next four service dates with the earliest and latest acceptable day, a weekly test rotation that reaches every call point, and the false alarm rate that decides whether the 2025 edition calls for an investigation. Print the page and the rotation becomes a log sheet.

The date on the last servicing certificate, or the date a new system was accepted.
Every break glass point on the system.
The day the rotation starts. Same weekday each week.
Smoke, heat and multi-sensor heads. 0 for a manual system.
From the log book.

Next service due 15 Dec 2026.

Any date from 15 Nov 2026 to 15 Jan 2027 is inside the 5 to 7 month window that BS 5839-1:2025 allows after the visit on 15 Jun 2026.

Service visits for the next two years

VisitEarliestDueLatestAlso at this visit
115 Nov 202615 Dec 202615 Jan 2027ARC signals, panel clock, false alarm rate
215 May 202715 Jun 202715 Jul 202712 months on: duct smoke detectors
315 Nov 202715 Dec 202715 Jan 2028ARC signals, panel clock, false alarm rate
415 May 202815 Jun 202815 Jul 202812 months on: duct smoke detectors

Assumes each visit happens on its due date. If your last visit was not a 12-monthly one, the 12-monthly items fall on visits 1 and 3 instead. Every visit checks ARC signals, the panel clock and the false alarm rate.

Weekly call point rotation

With 12 call points, each one is operated once every 12 weeks, so about 4.3 times a year by the weekly test alone.

WeekDateCall pointResultSignature
1Mon 23 Nov 2026CP 1
2Mon 30 Nov 2026CP 2
3Mon 7 Dec 2026CP 3
4Mon 14 Dec 2026CP 4
5Mon 21 Dec 2026CP 5
6Mon 28 Dec 2026CP 6
7Mon 4 Jan 2027CP 7
8Mon 11 Jan 2027CP 8
9Mon 18 Jan 2027CP 9
10Mon 25 Jan 2027CP 10
11Mon 1 Feb 2027CP 11
12Mon 8 Feb 2027CP 12

False alarm rate

1 / 40 x 100 = 2.5 false alarms per 100 detectors per year. Under 4 per 100. The servicing engineer still checks the rate at every visit.

Runs in your browser; nothing you type is sent anywhere. England and Wales.

Worked example

The last service was on 15 Jun 2026. Six months on is 15 Dec 2026. BS 5839-1:2025 recommends an inspection and service about every 6 months, and treats any visit from 5 to 7 months after the previous one as acceptable. The date the system was accepted is the starting point for these periods. So the next visit can be on any day from 15 Nov 2026 to 15 Jan 2027.

After 15 Jun 2026EarliestDueLatest
Visit 115 Nov 202615 Dec 202615 Jan 2027
Visit 215 May 202715 Jun 202715 Jul 2027
Visit 315 Nov 202715 Dec 202715 Jan 2028
Visit 415 May 202815 Jun 202815 Jul 2028

Sources: FIA guide to the changes in BS 5839-1:2025, IET Wiring Matters, November 2025. BS 5839-1 is sold by BSI and we have not reproduced it; the wording here is ours.

What the weekly test is

Once a week, during normal working hours, someone on site operates one manual call point, using a different one each week in strict rotation, and writes down which one was used. No engineer is needed. See the weekly fire alarm test.

Who uses this

Responsible persons, facilities and building managers who keep the log book, and fire alarm engineers who want the next due date and window for a site at a glance.

Before you rely on these dates

Questions

How often should a fire alarm be serviced?

About every 6 months under BS 5839-1:2025. The 2025 edition accepts any visit from 5 to 7 months after the previous one, with the date of acceptance as the starting point.

Is the planner a certificate?

No. It works out dates, a rotation and a rate. The inspection and servicing certificate comes from the competent person who services the system.

Does anything I type leave my browser?

No. The dates and numbers stay in your browser. The page counts that it was used, without the values.

Related

A service register for every site you look after

We are building a register for fire alarm engineers and building managers: every site's service dates and windows, weekly test rotations and false alarm rates in one place, with a reminder before a visit falls outside its window. Planned price £39 a month. Join the waitlist and we will email you when it opens. Nothing to pay now.