What BS 5839-1:2025 changed for maintenance

The 2025 edition replaced the 2017 edition. These are the changes that affect servicing and record keeping.

The date on the last servicing certificate, or the date a new system was accepted.
Every break glass point on the system.
The day the rotation starts. Same weekday each week.
Smoke, heat and multi-sensor heads. 0 for a manual system.
From the log book.

Next service due 1 Jan 2027.

Any date from 1 Dec 2026 to 1 Feb 2027 is inside the 5 to 7 month window that BS 5839-1:2025 allows after the visit on 1 Jul 2026.

Service visits for the next two years

VisitEarliestDueLatestAlso at this visit
11 Dec 20261 Jan 20271 Feb 2027ARC signals, panel clock, false alarm rate
21 Jun 20271 Jul 20271 Aug 202712 months on: duct smoke detectors
31 Dec 20271 Jan 20281 Feb 2028ARC signals, panel clock, false alarm rate
41 Jun 20281 Jul 20281 Aug 202812 months on: duct smoke detectors

Assumes each visit happens on its due date. If your last visit was not a 12-monthly one, the 12-monthly items fall on visits 1 and 3 instead. Every visit checks ARC signals, the panel clock and the false alarm rate.

Weekly call point rotation

With 12 call points, each one is operated once every 12 weeks, so about 4.3 times a year by the weekly test alone.

WeekDateCall pointResultSignature
1Mon 23 Nov 2026CP 1
2Mon 30 Nov 2026CP 2
3Mon 7 Dec 2026CP 3
4Mon 14 Dec 2026CP 4
5Mon 21 Dec 2026CP 5
6Mon 28 Dec 2026CP 6
7Mon 4 Jan 2027CP 7
8Mon 11 Jan 2027CP 8
9Mon 18 Jan 2027CP 9
10Mon 25 Jan 2027CP 10
11Mon 1 Feb 2027CP 11
12Mon 8 Feb 2027CP 12

False alarm rate

3 / 45 x 100 = 6.67 false alarms per 100 detectors per year. Over 5 per 100 on a system with more than 40 detectors: the 2025 edition calls for an in-depth investigation.

Runs in your browser; nothing you type is sent anywhere. England and Wales.

Servicing

Records

Sources: FIA guide to the changes in BS 5839-1:2025, IET Wiring Matters, November 2025. BS 5839-1 is sold by BSI and we have not reproduced it; the wording here is ours.

Before you rely on these dates

Questions

Where can I read the standard?

BS 5839-1:2025 is sold by BSI. The FIA and IET summaries linked on this page cover the changes.

Related

A service register for every site you look after

We are building a register for fire alarm engineers and building managers: every site's service dates and windows, weekly test rotations and false alarm rates in one place, with a reminder before a visit falls outside its window. Planned price £39 a month. Join the waitlist and we will email you when it opens. Nothing to pay now.